EasyManua.ls Logo

Eaton Cutler-Hammer DS Series - The Amptector II-A Trip Unit

Eaton Cutler-Hammer DS Series
93 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
l.B.
33·790·1
I
8.1
THE AMPTECTOR II-A TRIP UNIT
Improvements have been made to the Cutler-Hammer
Amptector and the standard model is now Amptector II-A.
Wiring and terminal changes were made to provide
method of testing with a tester. Refer to Section 8.7.6 for
testing with Amptector Test Kit.
Another change was to modify the long delay curve to
nearly an 1
2
T function. The revised curve shows this
change. See Curve
No.
1.
The Amptector II-A is standard equipment on all DS and
DSL circuit breakers. It provides approximately equiva-
lent functions as the electro-mechanical trip devices pro-
vided on some circuit breakers but with the superior
operating capability of solid-state devices. The Amptector
I-A is an optional (extra cost) tripping system which can
be provided when ground fault protection or trip indica-
tors are required. Both trip units have the same reliability
and repeatability inherent
in
solid-state design.
As shown
in
Figure 5 the Amptector trip unit is at the top
front of the breaker. Figure 60 shows a close-up of the
front of the Amptector II-A trip unit. There can be a total of
five adjustable controls, with screwdriver adjustment.
These are for setting the following characteristics:
1. Long-delay current pick-up.
LONG
DELAY
CURRENT--------------.
?!CKUP
0.5
to
1.25X
SENSOR
RATING
SHORT DELAY
CURRENT
PICKUP 4 TO
10X
SENSOR
RATING
INSTANTANEOU,
PICKUP 4
TO
12X
SENSOR
RATING
•see
Section
8.4
of
Text
for
Explanation
Fig.
61
Amptector II-A
Trip
Unit with Front Cover
Effective
October
1998
Page
55
2.
Long-delay time.
3.
Short-delay current pick-up.
4.
Short-delay time.
5.
Instantaneous current pick-up.
Note: The term "pick-up" as used here means the
rms value of current at which the Amptector trip unit
timing function begins or instantaneous tripping is
intiated.
Fig. 60 Standard Amptector II-A So/id-State
Trip
Unit
*
---*
Removed (396704)
Courtesy of NationalSwitchgear.com

Table of Contents

Related product manuals