Description Information Corrective Action
See also “The Waveform Recorder is permanently logging
new records”.
SW 10 Connection refused The protection device refused an incoming
connection because of certicate or encryption
problems.
This message typically results from a connection attempt
using some illegal client software (i. e. other than
PowerPort-E). You should check whether this indicates an
unauthorized access attempt.
SW 11 IEC104 queue over. There were more IEC104-related events
generated than could be handled. This resulted
in an IEC104 queue overow and corrupt
internal IEC104 data, so that the IEC104 protocol
has been disabled automatically. It can be re-
enabled by resetting the counters at [Operation/
Reset] »IEC104 . Res all Diag Cr«.
This message should not occur except in very uncommon
stress situations. Therefore we recommend to get in
contact with our service-team.
9www.eaton.comE-Series Family Troubleshooting Guide)