Description Information Corrective Action
See also “The Waveform Recorder is permanently logging
new records”.
SW 10 Connection refused The protection device refused an incoming
connection because of certi󰅰cate or encryption
problems.
This message typically results from a connection attempt
using some illegal client software (i. e. other than
PowerPort-E). You should check whether this indicates an
unauthorized access attempt.
SW 11 IEC104 queue over󰅱. There were more IEC104-related events
generated than could be handled. This resulted
in an IEC104 queue over󰅱ow and corrupt
internal IEC104 data, so that the IEC104 protocol
has been disabled automatically. It can be re-
enabled by resetting the counters at [Operation/
Reset] »IEC104 . Res all Diag Cr«.
This message should not occur except in very uncommon
stress situations. Therefore we recommend to get in
contact with our service-team.
9www.eaton.comE-Series Family Troubleshooting Guide)
2 Self-Supervision Messages
2.2 Self-Supervision – Warning Messages

Other manuals for Eaton E Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton E Series and is the answer not in the manual?

Eaton E Series Specifications

General IconGeneral
SeriesE Series
Operate Time15 ms
Contact ArrangementDPDT
Electrical Life100, 000 operations
Vibration Resistance10-55 Hz, 1.5 mm
Mechanical Life10, 000, 000 operations

Related product manuals