Keypad of the Drive
 
H-Max HVAC Drives
 
    MN04008004E—September 2011    www.eaton.com
 
5
 
Editing Values on Graphical Keypad
 
HOA Control Button
 
The HOA (Hand-Off-Auto) button is used for two functions: 
to quickly access the Control page and to easily change 
between the Hand (Keypad), Off, and Auto (Remote) control 
places.
 
Control Place
 
The 
 
control place
 
 is the source of control where the drive can 
be started and stopped. Every control place has its own 
parameter for selecting the frequency reference source. In 
the HVAC drive, the 
 
Hand control place
 
 is always the keypad. 
The 
 
Auto control place
 
 is determined by parameter P2.1.1 
(Keypad, I/O Terminal, I/O three-wire, or Fieldbus CTRL). The 
selected control place can be seen on the status bar of the 
keypad.
 
Local Control
 
The keypad is always used as control place while in hand 
control. Hand control has higher priority than auto control. 
Therefore, if, for example, bypassed by parameter P2.1.17 
through digital input while in 
 
Remote
 
, the control place will 
still switch to Keypad if 
 
Hand
 
 is selected. Switching between 
Hand, Off, and Auto Control can be done by pressing the 
HOA button on the keypad.
 
Changing Control Place
 
Change of control place from 
 
Hand
 
 to 
 
Auto
 
 (keypad).
1. Anywhere in the menu structure, push the HOA button.
2. Push the 
 
arrow up
 
 or the 
 
arrow down
 
 button to select 
 
Hand/Off/Auto
 
 and confirm with the OK button.
3. On the next display, select 
 
Hand
 
, 
 
Off
 
, or 
 
Auto
 
 and again 
confirm with the 
 
OK
 
 button.
4. The display will return to the same location as it was 
when the 
 
HOA
 
 button was pushed. However, if the 
Remote control place was changed to Hand (Keypad) 
you will be prompted for keypad reference.
STOP READY I/O
STOP READY I/O
STOP READY I/O
OK OK
OK
STOP READY I/O
STOP READY I/O
OR:
BACK
RESET