Step 4 — Parameter Groups & Default Values (Continued)
70 — PROTECTIVE 
80 — KEYPAD/DISPLAY
Modbus Groups Description Range Default
User
Settings
0500H 70.01 Over-voltage Stall 
Prevention
00: Disable 01
01: Enable
0501H 70.02 Over Current Stall 
Prevention during 
Acceleration
00: Disable
20 to 200%
150
0502H 70.03 Over Current Stall 
Prevention during 
Operation
00: Disable
20 to 200%
150
0503H 70.04 Over-Torque 
Detection Mode 
(OL2)
00: Disabled 00
01: Enabled during constant speed 
operation, drive halted after fault
02: Enabled during constant speed 
operation, operation continues after 
fault
03: Enabled during operation, drive 
halted after fault
04: Enabled during operation, 
operation continues after fault
0504H 70.05 Over-Torque 
Detection Level
30 to 200% 150
0505H 70.06 Over-Torque 
Detection Time
0.1 to 10.0 sec 0.1
0506H 70.07 Electronic Thermal 
Overload Relay 
00: Constant Torque 01
01: Variable Torque
02: Inactive
0507H 70.08 Electronic Thermal 
Motor Overload Time
30 to 300 sec 60
0508H 70.09 Auto Voltage 
Regulation (AVR)
00: AVR enabled 00
01: AVR disabled
02: AVR disabled during 
deceleration
03: AVR disabled during stop
0509H 70.10 Auto Energy-Saving 00: Disable 00
01: Enable
050AH 70.11 Under Current 
Detection Value
0.0 Disable 0.0
0.1 to No Load Amps
050BH 70.12 Under current 
Detection Mode
0 or 1 0
050CH 70.13 Under current 
Detection Time
0.0 to 20.0 sec. 1.0
Modbus Groups Description Range Default
User
Settings
0600H 80.01 Software Version
0601H 80.02 AC Drive Rated 
Current Display
##.#
0602H 80.03 Manufacturer Model 
Information
00: MVXF50#0-2 
(230V 1ph/3ph 1/2 hp)
##
01: MVX001#0-2 
(230V 1ph/3ph 1 hp)
02: MVX002#0-2 
(230V 1ph/3ph 2 hp)
03: MVX003#0-2 
(230V 1ph/3ph 3 hp)
04: MVX005#0-2 
(230V 3ph 5 hp)
05: MVX007#0-2 
(230V 3ph 7-1/2 hp)
06: Reserved
07: Reserved
 
MN04002001E.fm  Page 13  Thursday, April 13, 2006  11:11 AM