 UX with W-VACi circuit breaker  6063308 G01 01 14 July 2011 www.eaton.com 
 
2.1.3  Circuit Breaker or Contactor Unit Positions  
Each unit can be placed in any one of three positions: 
Insert / Removed position 
The unit is put / placed in the insert / 
removed position when: 
  The compartment door is open 
  The unit is moved to the front of the 
panel ready for insertion, or 
  The unit is moved completely out of 
the panel. 
 
Test position 
The unit is put / placed in the test 
position, when: 
  The unit is  in the panel but 
moved to the front of the 
compartment,  
  The primary contacts are 
disconnected, the shutters 
are closed and 
  The 58-pole secondary plug 
is connected (control over 
the operation of the unit is 
now possible ) 
  The compartment door can 
be opened. 
 
Service position 
The unit is put / placed in the service 
position, when: 
  The unit is fully inserted and 
engaged into the compartment. 
  The primary contacts are 
connected and  
  The 58-pole secondary plug is 
connected 
  The compartment door cannot be 
opened. 
  In emergency situations, the door 
interlock can be defeated with the 
use of tools. 
 
 
 
2.1.4  Cable connections 
Cables can be connected in a number of ways.  
Connection from the front or rear of the panel with cable 
lugs is standard.  
 
Besides primary cables, secondary and auxiliary cables 
may also be installed. 
 
1.  Spout containing fixed contact, cable side. 
2.  Current transformer. 
3.  Earth switch. 
4.  Power cable 
5.  Cable glanding plate 
 
 
 
 
Fig. 2-3 Cable connections