Power Xpert
®
 UX with W-VACi circuit breaker  6063308 G01 01 14 July 2011 www.eaton.com 
The adjacent illustration shows the assembly of the 
main busbar with a T-off: 
Top: Assembly for main busbar/T-off 630/800/1250 A  
Centre: Assembly for main busbar/T-off 2000/2500 A  
Bottom: Assembly for main busbar/T-off 3150 A. 
Fig. 3-8 Busbar connection for T-off 
 
3.4.2  Earthing busbars 
General 
The earthing busbar system is located in the bottom 
compartment of the panel and consists of a copper bar. 
 
To prevent against electrical shock: 
Earthing connections have to be properly made. 
Connect the Power Xpert
®
 earthing busbars to 
the earth connection of the building (local earth 
potential). 
 
Earthing busbars - coupling 
1.  Connect adjacent panel’s earthing busbar in the 
bottom part of the cable compartment. 
2.  Connect the earthing busbar of the Power Xpert
®
 UX 
installation to the earth point of the switchroom. 
3.  Remove all tools, equipment and materials from the 
compartment. 
 
Fig. 3-9 Bolts connection for earthing busbar 
1.  Bolt M8x35 
2.  Plain washer 8 
3.  Spring washer 8 
4.  Nut M8