Earthing switch 
Each cable panel can be fitted with a short-circuit-proof 
earthing switch fitted to the cable side. The earthing 
switch connects the connection points of the cable with 
the earthing busbar. A mechanical interlock ensures that 
the earthing switch is always open when the circuit 
breaker or contactor unit is in the connected position. 
The earthing switch can be closed only with the circuit 
breaker or contact unit is in the Test / Disconnected 
position or completely removed. 
 
The earthing switch can be locked with a padlock. 
Special locks are used in some installations, e.g. with the 
aid of a locking coil. 
 
2.1.9  Withdrawable units 
Power Xpert
®
 UX switchgear can contain a variety of 
switching/measuring equipment in circuit breaker 
compartment 
 
Withdrawable circuit breaker unit 
The circuit breaker is the W-VACi. 
W-VACi circuit breakers are provided with vacuum 
interrupters. This assembly is mounted on a switch 
cradle and racking mechanism. 
 
Electrical control signals are supplied from the low-
voltage compartment via a 58-pole secondary plug. 
Mechanical and electrical interlocks prevent unintentional 
switching. 
 
Refer to separate Operations and Maintenance Manual 
for the Circuit Breaker. 
 
Withdrawble contactor unit 
The vacuum contactor is ideal for controlling applications 
requiring a high number and frequency of switching 
operations and for AC motors. The contactor basically 
consist of a moulded resin monobloc, where the vacuum 
interrupters, moving apparatus, control electromagnet, 
multi-voltage control feeder and auxiliary accessories are 
housed.  
 
Refer to separate Operations and Maintenance Manual 
for the Contactor 
 
Withdrawable Voltage Transformer unit 
The Voltage transformer mounted on a withdrawable 
cradle with integral racking mechanism is used to 
measure the voltage of the busbar or cable side 
depending on configuration.  
 
Refer to separate Operations and Maintenance Manual 
for the Withdrawable Voltage Transformer Unit