4.1.1  Mechanical operation door open 
When the door is open the circuit breaker or contactor 
withdrawable unit can be operated directly from the 
controls mounted on the front of the unit. For full 
information refer to the individual operations and 
maintenance manual. 
 
If the control plug is connected then a full functional test of 
the unit is possible. 
 
The door cannot be opened when the unit is in the 
Service position.  To open the door make sure the 
unit is in the OFF position and it is racked out fully to 
the TEST position.  This will release the door 
interlock mechanism and the door can now be 
opened. 
Door Interlock Defeat Mechanism: To open the door 
in an emergency, remove two screws. 
 
 
4.1.2  Charging the closing spring 
 
For operating of the circuit breaker unit see the user 
manual of the W-VACi. 
 
1.  Secondary Connector 
2.  Manual Close Button 
3.  Closed/Open Indicator 
4.  Manual Open Button 
5.  Front Panel 
6.  Manual Charging Handle 
7.  Nameplate 
8.  Spring Charged/Discharged Indicator 
9.  Operation Counter 
 
 
 
 
Fig. 4-1 Door Interlock defeat operation