Power Xpert
®
 UX with W-VACi circuit breaker  6063308 G01 01 14 July 2011 www.eaton.com  
 
Unit: from Test to Service position. 
1.  Insert the 58-pole plug into the socket 
2.  Check that the unit is Off.  
3.  If there is an earthing switch on the panel, ensure it 
is switched Off. 
4.  Close the panel door of the compartment 
5.  Turn the knob (1) located in the centre bottom of the 
door anti-clockwise until the operating hole is free  
6.  Fit the hand crank to the drive shaft and push a little 
to unlock the spindle mechanism and the handle will 
rotate. 
7.  Turn the hand crank clockwise until the unit is fully 
inserted 
8.  Remove the hand crank. Releasing the interlocking 
mechanism, the hand crank has to be turned a little 
in the opposite direction until a spring is released 
and the operating hand crank is pushed back. 
9.  The unit is now locked in the Service position and is 
fully operational. 
 
Fig. 4-6 Placing the 58-pole plug into the socket 
 
 
Fig. 4-7 Rack IN-OUT with closed door 
 
4.2.3  Door interlock mechanism 
It is only possible to rack unit from Test position to 
Service position when door closed 
 
4.2.4  Withdrawing a unit 
Withdrawal from Service to Test position 
1.  Check that the unit is Off 
2.  Turn  the knob (1) located in the centre bottom of the 
door anti-clockwise until the operating hole is free  
3.  Fit the hand crank to the drive shaft and push a little 
to unlock the spindle mechanism 
4.  Turn the hand crank anti-clockwise until the unit is 
fully withdrawn and the handle is tight. 
5.  To release  the  interlocking mechanism the handle 
has to be  turned a little in the opposite direction until 
a spring is released and the handle crank is pushed 
back  
6.  Remove the hand crank. The unit is now in the Test 
position and the door can be opened.