Table 59. Outputs (Cont.).
P3. 2.11
b
Reference limit supervision value
ID 162
Minimum value:
0.00 Hz
Maximum value:
MaxFreq Hz
Default value:
0.00 Hz
Description:
Selects the reference frequency value supervised by the reference frequency limit supervision function.
P3. 2.12
b
Reference limit supervision hysteresis
ID 12203
Minimum value:
0.10 Hz
Maximum value:
1.00 Hz
Default value:
0.10 Hz
Description:
This value selects the bandwidth between when the reference limit supervision enables and disables.
P3. 2.13
b
Temperature limit supervision
ID 165
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = No limit;
1 = Low limit supervision; or
2 = High limit supervision.
Description:
Selects how the drives temperature limit supervision controller functions.
P3. 2.14
b
Temperature limit display
ID 1842
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = Enable DO;
1 = Warning (W/O S)/enable DO;
2 = Warning (W S)/enable DO; or
3 = Fault/enable DO.
Description:
Supervision display selection.
P3. 2.15
b
Temperature limit supervision value
ID 166
Minimum value:
-10.0°C
Maximum value:
75.0°C
Default value:
40.0°C
Description:
Selects the drive temperature value supervised by the drive temperature limit supervision function.
P3. 2.16
b
Temperature limit supervision hysteresis
ID 2204
Minimum value:
1.0°C
Maximum value:
10.0°C
Default value:
1.0°C
Description:
This value selects the bandwidth between when the temperature limit supervision enables and disables.
P3. 2.17
b
Power limit supervision
ID 167
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = No limit;
1 = Low limit supervision; or
2 = High limit supervision.
Description:
Selects how the drives power limit supervision controller function.
P3. 2.18
b
Power limit display
ID 1825
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = Enable DO;
1 = Warning (W/O S)/enable DO;
2 = Warning (W S)/enable DO; or
3 = Fault/enable DO.
Description:
Supervision display selection.
P3. 2.19
b
Power limit supervision value
ID 168
Minimum value:
-200.0%
Maximum value:
200.0%
Default value:
0.0%
Description:
Selects the output power value supervised by the power limit supervision function.
P3.2.20
b
Power limit supervision hysteresis
ID 2205
Minimum value:
0.1%
Maximum value:
10.0%
Default value:
0.1%
Description:
This value selects the bandwidth between when the power limit supervision enables and disables.