EasyManua.ls Logo

Eaton PowerXL DM1 Series - Page 189

Eaton PowerXL DM1 Series
258 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
179
Chapter 7- Multi-purpose application
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com
Table 59. Outputs (Cont.).
P3.2.21
b
AI supervision select
ID 170
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = Analog reference from AI; or
1 = Analog reference from keypad potentiometer.
Description:
Selects analog signal to use for the analog input supervision.
P3.2.22
b
AI limit supervision
ID 171
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = No limit;
1 = Low limit supervision; or
2 = High limit supervision.
Description:
Selects analog signal to use for the analog input supervision.
P3.2.23
b
AI limit display
ID 1826
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = Enable DO;
1 = Warning (W/O S)/enable DO;
2 = Warning (W S)/enable DO; or
3 = Fault/enable DO.
Description:
Supervision display selection.
P3.2.24
b
AI limit supervision value
ID 172
Minimum value:
1.00%
Maximum value:
10.00%
Default value:
0.00%
Description:
Selects the analog reference value supervised by the analog reference limit supervision function.
P3.2.25
b
AI supervision hysteresis
ID 2198
Minimum value:
1.00%
Maximum value:
10.00%
Default value:
1.00%
Description:
This value selects the bandwidth between when the AI supervision enables and disables.
P3.2.26
b
Motor current supervision
ID 2189
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = No limit;
1 = Low limit supervision; or
2 = High limit supervision.
Description:
Selects how the motor current limit supervision controller functions.
P3.2.27
b
Motor current limit display
ID 1827
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = Enable DO;
1 = Warning (W/O S)/enable DO;
2 = Warning (W S)/enable DO; or
3 = Fault/enable DO.
Description:
Supervision display selection.
P3.2.28
b
Motor current supervision value
ID 2190
Minimum value:
0.00 A
Maximum value:
DriveNomCurrCT*2 A
Default value:
DriveNomCurrCT A
Description:
Selects the motor current value supervised by the motor current limit supervision function.
P3.2.29
b
Motor current supervision hysteresis
ID 2196
Minimum value:
0.10 A
Maximum value:
1.00 A
Default value:
0.10 A
Description:
This value selects the bandwidth between when the motor current supervision enables and disables.

Table of Contents