Chapter 7- Multi-purpose application
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com
Table 59. Outputs (Cont.).
P3.3.2
b
AO function
ID 146
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
1
Options:
1 = Output frequency (0 -mMax frequency);
2 = Frequency reference (0 - max frequency);
3 = Motor speed RPM (0 - nameplate RPM);
4 = Motor current (0 - nameplate current);
5 = Motor torque (0 - calculated nominal);
6 = Motor power (0 - calculated nominal);
7 = Motor voltage (0 - nameplate voltage);
8 = DC bus voltage (0 - 1000 Vdc);
9 = PI setpoint (process unit minimum - process unit maximum);
10 = PI error value (process unit minimum - process unit maximum);
11 = PI output (process unit minimum- process unit maximum);
12 = Analog input (0% - 100%);
13 = Drive reference potentiometer (0% - 100%);
14 = Fieldbus process data input 1 (0% - 100%);
15 = Fieldbus process data input 2 (0% - 100%);
16 = Fieldbus process data input 3 (0% - 100%);
17 = Fieldbus process data input 4 (0% - 100%);
18 = Fieldbus process data input 5 (0% - 100%);
19 = Fieldbus process data input 6 (0% - 100%);
20 = Fieldbus process data input 7 (0% - 100%);
21 = Fieldbus process data input 8 (0% - 100%);
22 = User defined output (user defined minimum - user defined maximum);
23 = Motor torque (0% - 200%); or
24 = Motor power absolute value (0% - 100%).
Description:
Select the function desired to the terminal AO1.
P3.3.3
b
AO filter time
ID 147
Minimum value:
0.00 s
Maximum value:
10.00 s
Default value:
1.00 s
Description:
Defines the filter time applied to the analog output signal. Zero equals no filtering.
P3.3.4
b
AO custom minimum
ID 1863
Minimum value:
N.A .%
Maximum value:
N.A .%
Default value:
0.00%
Description:
Input axis start point x1, define AO function selected signal minimum value (percent) that user wants. Default value is 0.
Negative value shall be allowed for x1.
From (x1, y1) and (x2, y2) will get gain and offset. Then expected AO will calculate from gain and offset.
P3.3.5
b
AO custom maximum
ID 1865
Minimum value:
N.A .%
Maximum value:
N.A .%
Default value:
100.00%
Description:
Input axis end piont x2, define AO function selected signal maximum value (percent) that user wants.
Default value is 100%.
Negative value shall be allowed for x2.
From (x1,y1) and (x2,y2) will get gain and offset. Then expected AO will calculate from gain and offset.
Notes
Analog signal with faults (unfiltered).
Filtered analog signal.
Filter time constant at 63% of the set value.
t (s)
63%
AI
AO
AO
Filter
Time
AO1