192
Chapter 7- Multi-purpose application
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com
Table 61. Motor control (Cont.).
P5 .2.10
b
Motoring torque limit REV
ID 1838
Minimum value:
0.0%
Maximum value:
300.0%
Default value:
300.0%
Description:
Motoring torque limit in the reverse direction.
P5.2.11
b
Generator torque limit REV
ID 1839
Minimum value:
0.0%
Maximum value:
300.0%
Default value:
300.0%
Description:
Generation torque limit in the reverse direction.
P5 .2.12
b
Motoring power limit
ID 1607
Minimum value:
0.0%
Maximum value:
300.0%
Default value:
300.0%
Description:
Motor power limit setting.
P5 .2.13
b
Generator power limit
ID 1608
Minimum value:
0.0%
Maximum value:
300.0%
Default value:
300.0%
Description:
Generator power limit setting.
P5 .2.14
ab
Flux reference
ID 1620
Minimum value:
0.0%
Maximum value:
500.0%
Default value:
100.0%
Description:
This parameter defines the amount of flux that is output to the motor, which is valid only in open loop vector control.
P5 .2.15
a
PM initial selection
ID 1890
Minimum value:
N.S.
Maximum value:
N.A.
Default value:
1
Options:
0 = Align;
1 = Six pluse; or
2 = HFI.
Description:
PM initial angle detect method.
P5 .2.16
a
PM initial time
ID 1891
Minimum value:
0.0 s
Maximum value:
60.0 s
Default value:
0.7 s
Description:
PM initial angle detect time.
P5 .2.17
a
PM excited current
ID 1892
Minimum value:
0%
Maximum value:
200%
Default value:
20%
Description:
PM excited current during the low speed.
P5 .2.18
a
PM excited current off frequency
ID 1893
Minimum value:
10.00%
Maximum value:
MotorNomFreq %
Default value:
20.00%
Description:
PM excited current cut off frequency.
P5 .2.19
Observer Kp
ID 2901
Minimum value:
1%
Maximum value:
3,000%
Default value:
100%
Description:
Linear gain of the PM/IM observer.
a
Parameter value can only be changed after the drive has stopped.
b
Parameter value will be set to be default when changing macros.
Table 62. Protections (Cont.).
P6.1 - Motor.
P6.1.1
ab
Output phase fault
ID 308
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
2
Options:
0 = No response;
1 = Warning;
2 = Fault - stop mode after fault according to parameter stop mode; or
3 = Fault - stop mode after fault always by coasting.
Description:
Output phase supervision of the motor ensures that the motor phases have equal currents. If phases are 5% difference from one
another, the frequency converter will respond corresponding to this setting.
.