P2.1 - Basic settings.
P2.1.3
ab
IO terminal Start/Stop logic
ID 143
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = Forward - reverse: maintained input on start signal 1 to run forward and a maintained signal on start signal 2 for reverse.
1 = Start - reverse: maintained input on start signal 1 to maintain start signal 2 Open for forward, Close for reverse.
2 = Start - enable: maintained input on start signal 1 to run forward and a maintained signal on start signal 2 to enable the drive to run.
3 = Start pulse - Stop pulse: used for three wire operation. Start signal 1 uses a normally open start and start signal 2 uses a normally
closed stop.
Description:
Defines the functionality for start signal 1 and start signal 2. By default, start signal 1 is DI1 and start signal 2 is DI2.
0 = P2.2.1: DI closed contact = start forward P2.2.3: DI closed contact = start reverse. This would be considered 2-wire control
with either a contact used on the start FWD or start REV commands. When contacts open, the motor stops.
ID180
1 - St
art Signal: DigIN:1
24 V+
DIN1
1
DIN2
2
CMA
5
GND 12
ID143
St
art Stop L
ogic: St
art Forward
ID1803
- St art Signal 2: DigIN:2 ID1 43 St art Stop L ogic: Start Reverse
14
1
REV
DIN1
Output
Frequency
Stop Function
Stop Mode = Coasting
2 3
Notes: a
The first selected direction has the highest priority.
b
When the DIN1 contact opens the direction of rotation
starts to change.
c
If start forward (DIN1) and start reverse (DIN2) signals
are active simultaneously the start forward signal (DIN1)
has priority.
1 = P3.2: DI closed contact = start /open contact = stop P3.3: DI closed contact = reverse / open contact = forward. This would
be considered 2-wire control with a contact on start/stop, contact open it stops and direction on 2nd start signal.