24
Chapter 4 - Standard
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com
Table 10. Inputs (Cont.).
FWD
REV
DIN1
DIN2
Output
Frequency
Stop Function
Stop Mode = Coasting
t
2 = P3.2: DI closed contact = start/open contact = stop P3.3: DI closed contact = start enabled/open contact = start disabled and
drive stopped if running motor direction keeps forward. This would be considered 3-wire control with start signal 2 required
to be closed to enable start on start signal 1.
ID180
1 - St
art Signal: DigIN:1
24 V+
DIN1
1
DIN2
2
CMA
5
GND 12
ID143
St
art Stop L
ogic: St
art Forward
ID1803
- St art Signal 2: DigIN:2 ID1 43 St art Stop L ogic: Start Reverse
14
3 = Three-wire connection (pulse control): P3.2: DI changes from open to closed = start pulse P3.3: DI changes from closed to
open = stop pulse P3.5: DI closed contact = reverse/open contact = forward. This would be considered 3-wire control with
start signal 1 being the start pulse and start signal 2 being the NC stop.
ID180
1 - St
art Signal: DigIN:1
24 V+
DIN1
1
DIN2
2
CMA
5
GND 12
ID143
St
art Stop L
ogic: St
art Forward
ID1803
- St art Signal 2: DigIN:2 ID1 43 St art Stop L ogic: Start Reverse
14