UL cautions, warnings, and instructions
Wiring warnings for electrical practices and wire sizes
The Cautions, Warnings, and Instructions in this section summarize
the procedures necessary to ensure an inverter installation complies
with Underwriters Laboratories® guidelines.
Warning!
Use 60/75°C Cu wire only or equivalent.
Warning!
Open type equipment.
Warning!
Suitable for use on a circuit capable of
delivering not more than 5,000 rms
symmetrical amperes:
• 240 V maximum for DM1-32 models
• 500 V maximum for DM1-34 models
• 600 V maximum for DM1-35 models
Circuit breaker and fuse sizes
The adjustable frequency drives connections to input power must
include UL listed inverse time circuit breakers with 600 V rating, or
UL listed fuses.
Technical support contact information
Americas EMEA APAC
Website www.eaton.com/drives www.eaton.com/AfterSales www.eaton.com.cn/electrical
Email VFDaftermarketEG@eaton.com AfterSalesEGBonn@eaton.com CustomerServicePDCNA@eaton.com
Phone 1-877-386-2273 (8:00 a.m. to 6:00 p.m.
Eastern Time U. S. [UTC5])
800-543-7038 (6:00 p.m. to 8:00 a.m.
Eastern Time U.S. [UTC5])
TRCDrivesTechSupport@eaton.com
+49 (0) 180 5 223822 800 9881203
en
en
en
Wire connectors
Warning!
Field wiring connections must be made by a UL
listed and CSA certified ring lug terminal connec-
tor sized for the wire gauge being used. The
connector must be fixed using the crimping tool
specified by the connector manufacturer.
Motor overload protection
DM1 adjustable frequency drives provide solid-state motor overload
protection, which depends on the proper setting of the following
parameter: P5.1.2 “current limit.
“The setting range is (0.2 * rated current) to (2 * rated current).
Warning!
When two or more motors are connected
to the inverter, they cannot be protected by
the electronic overload protection. Install an
external thermal relay on each motor.