Step 1.
Lift the drive out from the carton, remove the packaging. The
magnetic cores and cable ties are only included in EMI version drive.
Step 2.
Screw mounting: Attach the drive to the mounting plate with
four M5x20 (or 3/16 in.) screws and four M5 (or 3/16 in.) nuts. The
opening dimension on the mounting plate should follow required
dimension (refer to the dimension drawing in the instruction leaflet).
Step 3. (EMI version only):
The input wires (including 3 line wires and 1 input grounding wire)
should run through the input magnetic core before connecting to
input terminal block and grounding hole. Use a cable tie to tie the
input magnetic cores to the input wires. The output wires (only 3
motor wires) should run through the output magnetic core before
connecting to output terminal block.
+
Screw mounting
Four M5x20 or 3/16 inch screws
Four M5 or 3/16 inch nuts
Torque: 3 N.m (26.6 lb/in.)
The output grounding wire should not run through the output
magnetic core. Use a cable tie to tie the output magnetic cores to
the output wires. The maximum distance between input / output
magnetic cores top surface and drive bottom surface is 100 mm
(3.94 in.). The height of input magnetic core is bigger than output
magnetic core for FR4. .
3 line wires
Input grounding wire
Output grounding wire
Max. distance: 100 mm (3.94 in.)
3 motor wires
Input magnetic core
Output magnetic core