14
Instruction Leaet PUB53675
Effective December 2021
PowerXL DM1 and DM1 Pro series VFD 
 
 
EATON www.eaton.com
Input power and motor cable stripping lengths
Table 3.  Stripping lengths.
Frame size Power wiring Motor wiring
A1 
in. (mm)
B1 
in. (mm)
C1 
in. (mm)
D1 
in. (mm).
A2 
in. (mm)
B2 
in. (mm)
C2 
in. (mm)
D2 
in. (mm)
FR1 0.39 (10) 2.76 (70) 0.39 (10) 2.76 (70) 0.39 (10) 2.76 (70) 0.39 (10) 2.76 (70)
FR2 0.47 (12) 2.76 (70) 0.47 (12) 2.76 (70) 0.47 (12) 2.76 (70) 0.47 (12) 2.76 (70)
FR3 0.47 (12) 3.54 (90) 0.47 (12) 3.54 (90) 0.47 (12) 3.54 (90) 0.47 (12) 3.54 (90)
FR4 0.79 (20) 4.53 (115) 0.79 (20) 4.53 (115) 0.79 (20) 4.53 (115) 0.79 (20) 4.53 (115)
ote: N For I/O / STO / Relay output wires, the stripping length = 0.236-0.276 in. (6-7 mm).
Table 4.  Connection sizes and torques.
Output rating Size and torque
Input voltage Frame 
size
Drive 
catalog 
number
CT/IH 
current 
amps
VT/IL 
current 
amps
Power 
wire size 
AWG 
(mm2)
Power wire 
torque 
in.-lb (N·m)
Ground 
wire size 
AWG 
(mm2)
Ground 
wire 
torque 
in.-lb (N·m)
Control 
wire size 
AWG (mm2)
Control 
wire torque 
in.-lb (N·m) 
AI/DI 
RO
100 Vac to 120 Vac 
50/60 Hz 
1 phase
FR1 DM1-111D6… 1.6 2.5 14 (2.5) 4.4 (0.5) 14 (2.5) 7.1 (0.8) 28-16 (0.5-1.5) 1.73 (0.2) 4.5 (0.5)
DM1-113D0… 3 4.8 14 (2.5) 4.4 (0.5) 14 (2.5) 7.1 (0.8) 28-16 (0.5-1.5) 1.73 (0.2) 4.5 (0.5)
FR2 DM1-114D8… 4.8 6.9 10 (6) 10.5 (1.2) 10 (6) 7.1 (0.8) 28-16 (0.5-1.5) 1.73 (0.2) 4.5 (0.5)
DM1-116D9… 6.9 7.8 10 (6) 10.5 (1.2) 10 (6) 7.1 (0.8) 28-16 (0.5-1.5) 1.73 (0.2) 4.5 (0.5)
200 Vac to 240 Vac 
50/60 Hz 
1 phase
FR1 DM1-121D6… 1.6 2.5 14 (2.5) 4.4 (0.5) 14 (2.5) 7.1 (0.8) 28-16 (0.5-1.5) 1.73 (0.2) 4.5 (0.5)
DM1-123D0… 3 4.8 14 (2.5) 4.4 (0.5) 14 (2.5) 7.1 (0.8) 28-16 (0.5-1.5) 1.73 (0.2) 4.5 (0.5)
DM1-124D8… 4.8 7.8 14 (2.5) 4.4 (0.5) 14 (2.5) 7.1 (0.8) 28-16 (0.5-1.5) 1.73 (0.2) 4.5 (0.5)
FR2 DM1-127D8… 7.8 11 10 (6) 10.5 (1.2) 10 (6) 7.1 (0.8) 28-16 (0.5-1.5) 1.73 (0.2) 4.5 (0.5)
DM1-12011… 11 17.5 10 (6) 10.5 (1.2) 10 (6) 7.1 (0.8) 28-16 (0.5-1.5) 1.73 (0.2) 4.5 (0.5)
FR3 D M1-12 0 17… 17.5 25.3 8 (10) 10.5 (1.2) 8 (10) 14.2 (1.6) 28-16 (0.5-1.5) 1.73 (0.2) 4.5 (0.5)
200 Vac to 240 Vac 
50/60 Hz 
3 phase
FR1 DM1-321D6… 1.6 2.5 14 (2.5) 4.4 (0.5) 14 (2.5) 7.1 (0.8) 28-16 (0.5-1.5) 1.73 (0.2) 4.5 (0.5)
DM1-323D0… 3 4.8 14 (2.5) 4.4 (0.5) 14 (2.5) 7.1 (0.8) 28-16 (0.5-1.5) 1.73 (0.2) 4.5 (0.5)
DM1-324D8… 4.8 7.8 14 (2.5) 4.4 (0.5) 12 (2.5) 7.1 (0.8) 28-16 (0.5-1.5) 1.73 (0.2) 4.5 (0.5)
DM1-327D8… 7.8 11 12 (4) 4.4 (0.5) 10 (4) 7.1 (0.8) 28-16 (0.5-1.5) 1.73 (0.2) 4.5 (0.5)
FR2 DM1-32011… 11 17.5 10 (6) 10.5 (1.2) 10 (6) 7.1 (0.8) 28-16 (0.5-1.5) 1.73 (0.2) 4.5 (0.5)
DM1-32017… 17.5 25.3 8 (10) 10.5 (1.2) 10 (10) 7.1 (0.8) 28-16 (0.5-1.5) 1.73 (0.2) 4.5 (0.5)
FR3 DM1-32025… 25.3 32.2 8 (10) 10.5 (1.2) 8 (10) 14.2 (1.6) 28-16 (0.5-1.5) 1.73 (0.2) 4.5 (0.5)
FR4 DM1-32032… 32.2 48.3 4 (25) 33 (3.73) 8 (16) 14.2 (1.6) 28-16 (0.5-1.5) 1.73 (0.2) 4.5 (0.5)
DM1-32048… 48.3 62.1 3 (35) 33 (3.73) 6 (16) 14.2 (1.6) 28-16 (0.5-1.5) 1.73 (0.2) 4.5 (0.5)