Trouble Shooting Actions for Inverter Faults Messages 
A)  Consistent Fault 
Conditions: The readings between two microprocessors of control board 
are not consistent. It could be caused by the DSP and/or other circuits not 
functioning properly. 
 
Corrective Actions: 
  Restart the PV Inverter. 
  If fault remains, disconnect the PV Inverter and contact the system 
installer. 
 
B)  FAN2 Lock (PV260/PV270) 
Conditions:  The  external  cooling  fan  of  PV  Inverter  is  not  working 
properly. 
 
Corrective Actions 
  Visually check the front cooling fan. If any obstacle is found, clean it. 
  If  the  top  fan  is  not  functioning  it  may  be  replaced  per  the 
instructions described in section 9.1. 
  If fault remains, disconnect the PV Inverter and contact the system 
installer. 
 
C)  Over Temperature: 
Conditions: The internal temperature is higher than normal value 
 
Corrective Actions: 
  Disconnect PV Inverter for a period (>30 minutes) and then restart 
the PV Inverter. 
  If fault remains, disconnect the PV Inverter and contact the system 
installer.    Select  a  new  location  for  the  installation  when  if  it  is 
necessary. 
   
D)  Relay Fault: 
Fault Conditions: The relay between inverter and grid is not functional 
 
Corrective Actions: 
  Restart the PV Inverter. 
  If fault remains, disconnect the PV Inverter and contact the system 
installer.