EasyManua.ls Logo

Ecoer EAHAEC-36 - 8.7.6 EH 0 E (Water-Level Alarm Malfunction Diagnosis and Solution)

Ecoer EAHAEC-36
157 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
103/157
SDi Decades Extreme Service Manual www.ecoer.com
May. 2023Manufacturer reserves the right to change specifications or designs without notice.
8.7.6 EH 0E(Water-Level Alarm Malfunction Diagnosis and Solution)
Description: If the sampling voltage is not 5V, the LED displays the failure code.
Recommended parts to prepare:
Connection wires
Water level switch
Indoor PCB
If the water-level switch is
broken?
Is the water-level switch
inserted properly?
Insert the water-level switch
properly
NO
YES
Replace the water-level switch
NO
Replace the indoor main PCB
Does a problem
remain?
YES
The unit is operating normally.
NO
Power off, then restart the unit 2 minutes later.
YES

Related product manuals