8.8 Check Procedures
8.8.1 Temperature Sensor Check
WARNING
Be sure to turn off all power supplies or disconnect all wires to avoid electric shock.
Operate after compressor and coil have returned to normal temperature in case of injury.
Note: The picture and the value are only for reference, actual condition and specific value may vary.
8.8.2 Compressor Check
1. Disconnect the compressor power cord from outdoor PCB (Refer to Chapter 10. Outdoor Unit Disassembly)).
2. Measure the resistance value of each winding using a multi-meter.
3. Check the resistance value of each winding in the following table.
1. Disconnect temperature sensor from PCB (Refer to Chapter 9. Indoor Disassembly and Chapter 10. Outdoor
Disassembly).
2. Measure the resistance value of the sensor using a multi-meter.
3. Check corresponding temperature sensor resistance value table (Refer to Chapter 11. Appendix).