EasyManua.ls Logo

Ecoer EAHAEC-36 - Product Features; 7.1 Display Function

Ecoer EAHAEC-36
157 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
67/157
SDi Decades Extreme Service Manual www.ecoer.com
May. 2023Manufacturer reserves the right to change specifications or designs without notice.
Mode
Priority
G
Y1
Y/Y2
B
W
W1
W2
E/AUX
DH/DS/BK
Display
Shut down
/
0
0
0
0
0
0
0
0
*
00
Fan
7
1
0
0
0
0
0
0
0
1
01
Fan
1
0
0
0
0
0
0
0
0
Cooling
6
*
1
0
0
0
0
0
0
1
02
Cooling 2
*
*
1
0
0
0
0
0
1
03
Dehumidification 1
*
1
0
0
0
0
0
0
0
04
Dehumidification 2
*
*
1
0
0
0
0
0
0
05
Heating 1
5
*
1
0
1
0
0
0
0
1
06
Heating 2
*
*
1
1
0
0
0
0
1
07
Heating 2
*
*
*
*
1
0
0
0
1
Electric heating 1
3
*
0
0
0
0
1
0
0
*
08
Electric heating 1
*
0
0
0
0
0
1
0
*
Electric heating 2
*
0
0
0
0
1
1
0
*
09
Heating 1+Electric heating 1
4
*
1
0
1
0
1
0
0
1
10
Heating 1+Electric heating 1
*
1
0
1
0
0
1
0
1
Heating 2+Electric heating 1
*
*
1
1
0
1
0
0
1
Heating 2+Electric heating 1
*
*
*
*
1
1
0
0
1
Heating 2+Electric heating 1
*
*
1
1
0
0
1
0
1
Heating 2+Electric heating 1
*
*
*
*
1
0
1
0
1
Heating 1+Electric heating 2
*
1
0
1
0
1
1
0
1
11
Heating 2+Electric heating 2
*
*
1
1
0
1
1
0
1
Heating 2+Electric heating 2
*
*
*
*
1
1
1
0
1
Emergency heating
1
*
*
*
*
*
*
*
1
*
12
Heating zone control
2
*
1
0
1
0
*
*
0
0
13
Heating zone control
*
*
1
1
0
*
*
0
0
Heating zone control
*
*
*
*
1
*
*
0
0
NOTICE:
1 : signal
0 : no signal
If the input does not meet the above, press shutdown for processing.