EasyManua.ls Logo

Ecoer EAHAEC-36 - 8.8.4 4-way Valve Check

Ecoer EAHAEC-36
157 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
128/157
SDi Decades Extreme Service Manual www.ecoer.com
May. 2023Manufacturer reserves the right to change specifications or designs without notice.
8.8.4 4-way Valve Check
1. Power on, use a digital tester to measure the voltage, when the unit operates in cooling, it is 0V. When the unit
operates in heating, it is about 230VAC.
If the value of the voltage is not in the range, the PCB must have problems and need to be replaced.
2 Turn off the power, use a digital tester to measure the resistance. The value should be 1.8~2.5 KΩ .

Related product manuals