SDi Decades Extreme Service Manual www.ecoer.com
May. 2023Manufacturer reserves the right to change specifications or designs without notice.
Procedure
Illustration
3) Pull out the auxiliary heat module. (see
AHU_15)
4) Pull out the wire connect to the fuse
with needle-nose pliers(see AHU_16)
Note: Qty of EAH-03B&EAH-05B is 1, Qty of
EAH-08B&EAH-10B is 2, Qty of EAH-15B
is 3, Qty of EAH-20B is 4, Qty of EAH-25B is
5.
5) Loosen the retaining nut, and then
remove the fuse. (see AHU_17)
AHU_15
Fuse
AHU_16
AHU_17
Note: This section is for reference only. Actual unit appearance may vary.