Start up - Operting check
Operating check
Flame monitoring must be checked
for safety as part of initial
commissioning and also after servicing or
if the system has been out of operation for
any significant period of time.
- Start attempt with gas ball valve closed:
the automatic combustion control unit must
switch to gas shortage or malfunction after
the end of the safety period.