IO Board Communication Error
Occurs when communication is lost to the IO board.
Causes:
- Poor/broken communication cable connection
- Faulty IO board
Effect: System will not operate.
Contact Ecolab Service Personnel
Alarm can’t
be cleared.
Service
required.
Product Empty for Pocket X (solid product)
Occurs when conductivity reading does not reach
expected level.
Causes:
- Empty product container
- System plug at or downstream of sump screen
Effects:
- Product X will not dose
- Formula Not Finished alarm will occur at end of wash
formula
Product Empty for Pump X (liquid product)
Occurs when liquid product level sensor triggers out of
product.
Causes:
- Liquid product container is empty.
- Liquid product level sensor is faulty or disconnected.
Effects:
- Liquid product pump for triggered product will not
pump.
- Formula Not Finished alarm will occur at end of wash
formula
2. Programming
To enter the programming mode, press and hold the Center <Enter> key for 4+ seconds from the main screen. The controller
should prompt the user for a password.