4 Operations Manual
Note:
The operator has one hour to complete a panel (address) test.
After 1 hour, the address is automatically removed from the Test mode
and restored to normal operation.
Press the Test/Stat button. The display shows the following:
1) Test 2) Status 3) Sensitivity Report
4) History Enter # Choice ->_
The Test/Prgm LED flashes.
Key in “1” (Test) and press the Enter button. The display shows the
following:
Enter Test Panel Address DEL to Abort
Enter # Choice (pp)->_
The panel address is in the test mode. To remove the panel address
from the Walk Test mode, use the procedure above and press Delete
after entering the panel address.
Notes
1. Only one panel address may be in the test mode at one time. Sensors
and modules on the same ZAS line must be tested separately.
2. If an alarm occurs in a panel (address) NOT in the Test mode, the
Test panel (address) will automatically revert to normal mode of
operation.
The balance of the system remains operational. The entire network may
be tested by repeating this step, using a different panel address each
time. Only one standard device may be alarmed on a traditional zone.
The panel must then be manually Reset.
Test mode is canceled upon receipt of a new alarm condition.
Key in panel address and press the Enter button. The display shows
the following:
01:01:01 APXXXX DPXXXX
All Off normal device conditions will be listed on the printer. Remove
panel address from test mode when testing is complete.
Status
Displays system, circuit, and device condition.
Press the Test/Stat button. The display shows the following:
1) Test 2) Status 3) Sensitivity Report
4) History Enter # Choice ->_
The Test/Prgm LED flashes.
Key in “2” (Status) and press the Enter button. The display shows
the following: