Operations Manual 5
@ Copyright Edwards Systems Technology
1996, Ver X.XX.XX. Press Next to scroll
• Press the Next/Ack button to scroll the display. The display shows
the following:
Power Supply Status 1=OK, Next to scroll
Fuz1/gnd1/Acp1/Vlt1/Bat1/Ext1/Int1/Prn1
Fuz = Fuse
Gnd = Ground Fault
Acp = AC Voltage
Vlt = DC Voltage
Bat = Battery
Ext = Trouble
Int = Internal Fault (ZAS Card/continuity jumper)
Prn = Printer
1 = OK
0 = Fault
• Press the Next/Ack button to scroll the display. If a ZAS-2 Card is
installed in slot P5 of the control panel motherboard, the display
shows the following:
Zas2 @ card1 status. Use Next to scroll
Com1/Res1/Zas1/Mpg1/Mpe1/Gnd1/Lin1/Map0
Com = ZAS-2 Communication Flag
Res = Reset in Progress
Zas = ZAS-2 Internal Trouble
Mpg = ZAS-2 Mapping in Progress
Mpe = Mapping Enabled
Gnd = ZAS-2 Card Ground Fault
Lin = ZAS-2 Class A Fault
Map = ZAS-2 Map Fault
1 = OK (completed)
0 = Fault (in progress)
• Press the Next/Ack button to scroll the display. If a ZAS-2 Card is
installed in slot P6 of the control panel motherboard, the display
shows the following:
Zas2 @ card2 status. Use Next to scroll
Com1/Res1/Zas1/Mpg1/Prg1/Gnd1/Lin1/Map0
• Press the Next/Ack button to scroll the display. The display shows
the following:
Field Panel status use Next to scroll
Pnl#05/Power OK/CommA OK/CommB NG/Comm EN
Pnl#05 = Panel Address 05
Power = Panel Power Status (OK, or NG=no good)
CommA = Primary Communications (OK, or NG=no good)
CommB = Secondary Communications (OK, or NG=no good)
Comm = Communications (EN=enable, DS=disable)