Operations Manual 15
Key in “7“ (Seqnc) and press the Enter button. The display shows
the following:
Enable a Sequence
Enter Sequence # (nnnn) ->_
Key in the 4-digit sequence # that you want to enable and press the
Enter button.
The selected sequence is enabled. The display returns to normal.
Disable Functions
Disables a zone (except output zones), zone message, time control, data
line, panel, action, or sequence.
Notes
1. A level 1 or 2 password is required to disable system functions.
2. Completion of an enable/disable function returns the display back to
the ENABL/DSABL menu shown above. Additional sub-menu
selections can then be made.
Press the ENABL/DSABL button. The display shows the following:
1) Enable 2) Disable
Enter # Choice ->_
Key in “2“ (Disable) and press the Enter button. The display shows
the following:
1) Zone 2) Znmsg 3) Tmctrl 4) Datlne 5) Panel
6) Actn 7) Seqnc Enter Choice->_
Key in the appropriate password and press the Enter button. The
display shows the following:
Enter password level 2 ->_
From this point forward, the Disable procedure is the same as the
Enable procedure explained in previously.
Notes
1. Disabling a zone, zone message, data line, panel, action, or
sequence increments the DP (Disabled Points) counter.
2. Device/zone points that are disabled manually will sound a trouble
buzzer and illuminate the trouble LED.
3. Disabling through the program will not sound the trouble buzzer,
but will increment the DP counter.
4. You CANNOT disable an Output.