14 Operations Manual
The selected time control is enabled. The display returns to normal.
Enable Data Line
1) Zone 2) Znmsg 3) Tmctrl 4) Datlne 5) Panel
6) Actn 7) Seqnc Enter Choice->_
Key in “4“ (DatLne) and press the Enter button. The display shows
the following:
Enable a Communications Channel
Enter Com Channel (0/1) ->_
Key in “0” or “1” depending on the communications channel that
you want to enable and press the Enter button.
The selected communications channel is enabled. The display returns
to normal.
Enable Panel
1) Zone 2) Znmsg 3) Tmctrl 4) Datlne 5) Panel
6) Actn 7) Seqnc Enter Choice->_
Key in “5“ (Panel) and press the Enter button. The display shows
the following:
Enable a Panel’s Communications
Enter Panel Address (aa) ->_
Key in the 2-digit panel address that you want to enable and press
the Enter button.
Communications for the selected panel address is enabled. The display
returns to normal.
Enable Action
1) Zone 2) Znmsg 3) Tmctrl 4) Datlne 5) Panel
6) Actn 7) Seqnc Enter Choice->_
Key in “6“ (Actn) and press the Enter button. The display shows the
following:
Enable an Action
Enter Action # (nnnn) ->_
Key in the 4-digit action # that you want to enable and press the
Enter button.
The selected action is enabled. The display returns to normal.
Enable Sequence
1) Zone 2) Znmsg 3) Tmctrl 4) Datlne 5) Panel
6) Actn 7) Seqnc Enter Choice->_