Operations Manual 17
• Key in the 4-digit action # that you want to activate and press the
Enter button.
The selected action is activated. The display returns to normal.
Activate Sequence
• Press the ACT/Reset button. The display shows the following:
1) Activate 2) Reset
Enter # Choice->_
• Key in “1“ (Activate) and press the Enter button. The display shows
the following:
1) Output 2) Action 3) Seqnc 4) Smoke Lv.1
5) Smoke Lv.2 Enter # Choice->_
• Key in “3“ (Sequence) and press the Enter button. The display
shows the following:
Activate a Sequence
Enter Sequence # (nnnn) ->_
• Key in the 4-digit sequence # that you want to activate and press the
Enter button.
The selected sequence is activated. The display returns to normal.
Activate Smoke Level 1 or 2
Used to activate smoke sensitivity level 1 or 2.
• Press the ACT/Reset button. The display shows the following:
1) Activate 2) Reset
Enter # Choice->_
• Key in “1“ (Activate) and press the Enter button. The display shows
the following:
1) Output 2) Action 3) Seqnc 4) Smoke Lv.1
5) Smoke Lv.2 Enter # Choice->_
• Key in “4“ (Smoke Lv.1) or “5” (Smoke Lv.2) and press the Enter
button. The display shows the following:
Activate Smoke Lv.X
Smoke Lv.1 = Primary smoke sensitivity level setting.
Smoke Lv.2 = Alternate smoke sensitivity level setting.
The selected smoke sensitivity level is activated. The display returns to
normal.