18 Operations Manual
Reset Output
Press the ACT/Reset button. The display shows the following:
1) Activate 2) Reset
Enter # Choice->_
Key in “2“ (Reset) and press the Enter button. The display shows
the following:
1) Output 2) Action 3) Seqnc 4) Panel
5) Verf. Hist. Enter # Choice->_
Key in “1“ (Output) and press the Enter button. The display shows
the following:
Reset Output (Priority/panel#/device)
Enter Device Address (PPppdd)->_
Key in the priority, the panel #, and the device #, and press the Enter
button.
Example: 500207
PP = Priority = 50
pp = Panel # = 02
dd = Device # = 07
The selected device is reset. The display returns to normal.
Reset Action
Press the ACT/Reset button. The display shows the following:
1) Activate 2) Reset
Enter # Choice->_
Key in “2“ (Reset) and press the Enter button. The display shows
the following:
1) Output 2) Action 3) Seqnc 4) Panel
5) Verf. Hist. Enter # Choice->_
Key in “2“ (Action) and press the Enter button. The display shows
the following:
Reset an Action
Enter Action # (nnnn)->_
Key in the 4-digit action # that you want to activate and press the
Enter button.
The selected action is reset. The display returns to normal.
Reset Sequence
Press the ACT/Reset button. The display shows the following: