Chapter 3: Commissioning
LaserSense Nano Aspirating Smoke Detector Installers Handbook 31
1. Connect a 3.25-foot (1-meter) length of wire to a 6 VAC source of at least
16 Amps rating per wire for a period of 1 minute.
2. The system will respond within 120 seconds following de-energization. After
this period, most of the insulation should be burned off.
Note: The wire cross-section should be American Wire Gauge (AWG) 10 with
the following diameter and area:
Diameter = 2.59 mm or 0.10189 in.
Cross-section area = 5.0 mm² or 0.00775 in.²