EasyManuals Logo

Edwards LaserSense Nano User Manual

Edwards LaserSense Nano
58 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #53 background imageLoading...
Page #53 background image
Appendix A: Communications card and APIC
LaserSense Nano Aspirating Smoke Detector Installers Handbook 47
38 0 1 1 0 0 1 0 0 103 1 1 1 0 0 1 1 0
39 1 1 1 0 0 1 0 0 104 0 0 0 1 0 1 1 0
40 0 0 0 1 0 1 0 0 105 1 0 0 1 0 1 1 0
41 1 0 0 1 0 1 0 0 106 0 1 0 1 0 1 1 0
42 0 1 0 1 0 1 0 0 107 1 1 0 1 0 1 1 0
43 1 1 0 1 0 1 0 0 108 0 0 1 1 0 1 1 0
44 0 0 1 1 0 1 0 0 109 1 0 1 1 0 1 1 0
45 1 0 1 1 0 1 0 0 110 0 1 1 1 0 1 1 0
46 0 1 1 1 0 1 0 0 111 1 1 1 1 0 1 1 0
47 1 1 1 1 0 1 0 0 112 0 0 0 0 1 1 1 0
48 0 0 0 0 1 1 0 0 113 1 0 0 0 1 1 1 0
49 1 0 0 0 1 1 0 0 114 0 1 0 0 1 1 1 0
50 0 1 0 0 1 1 0 0 115 1 1 0 0 1 1 1 0
51 1 1 0 0 1 1 0 0 116 0 0 1 0 1 1 1 0
52 0 0 1 0 1 1 0 0 117 1 0 1 0 1 1 1 0
53 1 0 1 0 1 1 0 0 118 0 1 1 0 1 1 1 0
54 0 1 1 0 1 1 0 0 119 1 1 1 0 1 1 1 0
55 1 1 1 0 1 1 0 0 120 0 0 0 1 1 1 1 0
56 0 0 0 1 1 1 0 0 121 1 0 0 1 1 1 1 0
57 1 0 0 1 1 1 0 0 122 0 1 0 1 1 1 1 0
58 0 1 0 1 1 1 0 0 123 1 1 0 1 1 1 1 0
59 1 1 0 1 1 1 0 0 124 0 0 1 1 1 1 1 0
60 0 0 1 1 1 1 0 0 125 1 0 1 1 1 1 1 0
61 1 0 1 1 1 1 0 0 126 0 1 1 1 1 1 1 0
62 0 1 1 1 1 1 0 0 127 1 1 1 1 1 1 1 0
63 1 1 1 1 1 1 0 0
64 0 0 0 0 0 0 1 0
Optional APIC
When a command module is being used to manage one or more detectors (the
maximum limit is 127) an addressable protocol interface card (APIC) is required
to decode detector status information in the command module and convey to the
Fire Panel via the Addressable Bus 1 and Bus 2 terminal block connections (see
“Electrical installation” on page 19 for details). In this configuration only one
interface is required and all detector information is available through this
interface, one address per device.
Note: Either an optional communication card or an APIC can be installed in the
detector, not both. They are mounted the same and use the same connection on
the detector main PCB.
APICs plug into the main PCB via a ribbon cable (see Figure 14 on page 44).
Once plugged in, the addressable signaling line circuit (SLC) in and out are
connected to the main PCB addressable bus terminals and the address DIP
switches are set to the SLC address. Refer to the APIC installation sheet for
details.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Edwards LaserSense Nano and is the answer not in the manual?

Edwards LaserSense Nano Specifications

General IconGeneral
BrandEdwards
ModelLaserSense Nano
CategorySmoke Alarm
LanguageEnglish

Related product manuals