Connection – Page 93
Solar
inverter
|
V1.7
The buzzer beeps. After 10 minutes, the inverter
stops charging and discharging the lithium
battery
.
The loss of communication occurs once the
inverter and the battery are successfully
connected. The buzzer sounds
immediately
.
If the battery status cannot be charged through
successful communication between the inverter and
the battery, code 69 is displayed to stop the charging
of the
battery
.
If the battery status must be charged after the
communication between the inverter and the
battery was successful, code 70 is displayed for
the charging of the battery.
If the battery status cannot be discharged through
successful communication between the inverter and
the battery, code 71 is displayed to stop the
discharging of the battery.
9.8.5 Dry contact
There is a dry contact (3 A/250 VAC) on the back of the device. It can be used to send
signals to an external device when certain conditions are
met
:
Status
Operation
Dry contact
p
ort
:
NC & C
NO & C
Switching off
Power Off
Device is switched off and no output is supplied with
power
.
closed
open
Switching on
Power On
The output is supplied with power via the
mains power
supply
.
closed
open