Functions
Fire-alarm 1 function – if 24VDC is connected to the fire alarm input
terminal, the unit will simulate a mains failure, and activate all the outputs on
battery mode.
Fire-alarm 2 function – if 24VDC is connected to the fire alarm input
terminal, the unit activate all the outputs on mains.
Fire-alarm 3 function – if 24VDC is connected to the fire alarm input
terminal, the unit deactivate all the outputs.
Autotest – Battery test – If this function is selected in the settings,
the unit will test the status of the batteries every week, for a period of 10 minutes.
The battery power during discharge is compared to the selected battery size and
the final battery voltage. The point of departure for the test is that the battery is
fully charged and that the load is stable during the entire test. Once the test has
been performed, the unit will return to normal mode and display an error message
if the test has not been approved. Press the <Accept> button to approve. The
under voltage protection low battery (22 V) is active and will, if necessary, finish
the test and display an error message.