Technical specifications and data are subject to change without any prior notice.
22
Manual test function During normal operation, both buttons
may be pressed simultaneously, bringing up a selection between WEEKLY TEST
and ANNUAL TEST.
If selecting WEEKLY TEST (left-hand button), a load test will be performed for
20 minutes, indicated by a red LED diode TEST. Afterwards, a battery test will be
performed for 10 minutes, indicated by red LED diodes TEST and BATTERY
MODE.
If selecting ANNUAL TEST, the unit will perform a one-hour battery discharge,
with a countdown on the right side of the display. If the battery cannot take 1
hour (to low battery alarm), the unit will interrupt the test and sound an alarm, and
keeps the number of remaining minutes in the display. If the buttons are pressed
once again during the test, the unit will finish the test without updating the
memory.
Note that if the battery is not charge to 100 %, values may differ, resulting in an
alarm.