Overload:
Accept XXX VA
The unit has found that the load it supplies is larger than what it has been
designed for.
Remove load until it’s within specifications for the unit. If the unit gives of this
alarm on with the inverter on idle, notify your retailer.
Short Circuit:
The unit has during battery mode discovered a short circuit on the load, or that it
has a substantial overload
Remove the short circuit or the overload. Restart the unit.
If the alarm appear when idling on battery mode or if the load is else way
measured and controlled, contact your retailer.
Saturation detect:
The unit has a problem to supply the load during battery mode.
Remove the load that’s causing the problem. Press the right button to reset the
alarm and try to restart the load using the battery mode.
If the alarm appears when idling on battery, contact your retailer.
Earth fault:
The unit has discovered a difference between the output current to the load in
comparison to the received current from the load in the neutral. If this current
exceeds the chosen setting, the unit will shut of the load one output at a time until
it has found the cause of the problem.
The unit has to be shut down completely and restarted to reset this alarm.
Remove the earth leakage on the load or remove the output where it’s located. It’s
also possible to change the setting of the earth fault 100 mA or 300 mA.
Then restart the unit.
Multiple Earth fault:
The unit has discovered a difference between the output current to the load in
comparison to the received current from the load in the neutral. If this current
exceeds the chosen setting, the unit will shut of the load one output at a time until
it has found the cause of the problem.
If the unit can’t locate the fault to one single output it will shut down all the
outputs and give the alarm multiple earth fault.
The unit has to be shut down completely and restarted to reset this alarm.
Remove the earth leakage on the load or remove the output where it’s located. It’s
also possible to change the setting of the earth fault 100 mA or 300 mA.
Then restart the unit.