7.2 Operating Manual for the UPS
The operator of this UPS system must always observe the instructions in
this manual. The operator may only undertake the following listed
measures and only with particular care:
Using the operating elements: switch on, start and switch off the
UPS.
Reading the display elements and interpreting the acoustic warnings.
Starting the test operation.
Using the communication interface, whereby the connection to a
computer or other systems must already be present with UPS equip-
ment that have a permanent connection.
The extensive protective functions that the UPS system performs with re-
gard to the load(s) means that the UPS works completely automatically.
Only the switching on and starting or switching off is done by the opera-
tor. Furthermore, a data exchange can take place via the communication
interface and/or the SNMP adapter, although this is not absolutely neces-
sary for general operation of the system.
7.2.1 Switching on and starting the UPS
To switch on the UPS, connect the UPS with the supply mains by inserting the
power cable.
Make sure that the mains fuse (back of the device) is inserted. Before initially
starting the UPS, the basic settings must be checked.
The UPS is started by simultaneously pressing both the key "Menu selection"
and "Menu down" (hold down for approx. 3 sec.). Press the "POWER
ON/OFF" key for approx. 3 sec. for the types 1000RM - 1500RM.
After finishing the start procedure, the UPS reaches the appropriate type of
operation.