II
MICROVIP3 PLUS
SET UP PAGES
SHORT FORM
PAG
PAG PAG
SEL SEL
12 pages of three-phase measurements
7 pages of single-phase measurements Use SEL and
SET to select
baud rate
(1200
,
2400,4800,9600
,
19200,38400
),
* Note 1: these 3 pages are present only when LOG off. data bits (7/8),
stop bits (1/2),
parity (no/e/o).
PAG
PAG PAG PAG PAG PAG PAG PAG PAG PAG
SET SET SET SET SET
Use SEL and SET Use SET Use SEL
to select PT primary to select and SET
(from 1 to 999999 V) 1,2,5,10 to select
and PT secondary 15,20,30, from 1 to
(57.7,63.5,100,110,115, 60 minutes. SET 99 minutes
120,173,190,200,220 V), SET SET of data Press PAG
CT primary (from 1 to recording to clear
999999 A) and CT rate. internal
secondary (from 0.01 SET 00 = 3" memory;
to 1.00 V). SET SET display blinks
for 5"-10"
.
SET Std LOG = rms values
Sample LOG = V,I waveforms samples
Std1: kWh,kvarh SET Changing LOG type and confirming
Std2: kWh,kVAh by PAG., makes the display blinking
COG:
±
kWh,
±
kvarh for 5" -10".
Fundamental frequency
selection: 50 Hz or 60 Hz;
OFF = no harmonic
measurements and printouts.
Fnd = thd referred to the fundamental
instead of rms value.
SEt-UP MEAS
V
000100
P.t. 100
A
000005
C.t. 1.00
Std1
OPtio
n
m
Int 15
tiME
thd
50 Hz
*
Std
OG
*
m
LOG 01
rAtE
*
LOG no
LEAr
k
COM 9.60
n 7 1
Std2
OPtion
COG4
OPtion
thd
FF
SAMPLE
LOG
LOG YES
CLEAr
StAr
inSErt
dELtA
inSErt
2 PH
inSErt
thd
Fnd 50 Hz
thd
Fnd 60 Hz
thd
0Hz