EasyManua.ls Logo

Elcontrol Microvip 3 plus - THE ON BOARD MEMORY; TECHNICAL SPECIFICATIONS; GENERAL FEATURES

Elcontrol Microvip 3 plus
65 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
35
7 THE ON BOARD MEMORY
The on board memory is a 1 Mbyte non-volatile flash memory for data storage over extended surveys periods including
waveform capture for current and voltage.
Two different LOG types are selectable:
- In Standard LOG, Max 7840 records of all the measurements are available after a memory reset.
- In Sample LOG, Max 677 records of all Voltages and Currents waveforms are available after a memory reset.
Data recording rate is selectable from 1 to 99 minutes.
Fast data downloading to PC is provided via a high-speed RS232C serial link and based on WIN 95/98 and NT 4.0
software MicroWin.
8 TECHNICAL SPECIFICATIONS
8.1 GENERAL FEATURES
Inputs:
L1, L2, L3, N, I1, I2, I3.
Input specifications:
Voltage: (L1-N, L2-N, L3-N) direct inputs max 600 Vrms (STAR);
(L1-L3, L2-L3, L1-L2) direct inputs max 600 Vrms (DELTA) from 0 to 600 Hz;
up to 999999 V (with external PTs whose primary and secondary are selectable).
Input impedance: 4 M
Current: (I1, I2, I3) direct inputs 1 Vrms up to 600 Hz, or 1 VDC;
1000A from 30 to 600 Hz (with standard AC clamp meters);
from 0 to 600 Hz (with optional AC/DC clamp meters);
up to 999999 A (with external CTs whose primary and secondary are selectable).
Input impedance: 10 k
Voltmeter input overload:
maximum acceptable voltage 625 Vrms, peak voltage 825V.
Current input overload:
5 times full scale value (with protection trip at threshold value).
Units of measurement:
m, k, M, W, V, A, VA, Var, Hz, Wh, VArh, VAh, P.F. Cosø, THDF.
Measurement frequency:
1,2 seconds without harmonics - 2,5 seconds with harmonics.
Number of scales:
3 voltage scales; 3 current scales with automatic scale change.
Automatic scale change:
Scale change response time: 1,2 secs
Change to higher scale takes place at 105% active scale.
Change to lower scale takes place at 20% of active scale.
Clock:
Quartz, output to LCD
Printed date and time output.
Batteries:
One Ni-Cd 6V 940mAh battery of five 1,2V 940mAh elements in series, giving autonomy of approximately 7 hours
without printing and display backlight. Battery recharge time: 24 hours (from mains).
One 3,5V 280mAh lithium battery as memory buffer (guaranteeing memory backup for approximately 7 years).
IMPORTANT: when the lithium back-up battery is changed, date and time are lost.
Battery replacement must be carried out by qualified, authorized staff at ELCONTROL ENERGY service centres.
Measurement display:
Backlight LCD with temperature range of -30°C to +80°C.
Clock display:
4 digit LCD with temperature range of -10°C to +60°C.
Dimensions:
251 x 239 x 104 mm.
Instrument weight:
2,9 Kg.
Weight of MICROVIP3 PLUS KIT:
6,3 Kg.
Degree of protection : IP 40