EasyManua.ls Logo

Elcontrol Microvip 3 plus - Page 52

Elcontrol Microvip 3 plus
65 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
47
-AA = 01= address of the MICROVIP3 PLUS selected (2 bytes ascii)
-03H = Code of the command for reading of N words (2 bytes ascii)
-0000 = address from which the reading starts (4 bytes ascii)
-0001 = Number of words to be read (2 bytes ascii)
-LRC = Longitudinal Redundancy Check (2 bytes ascii)
-CR = 0DH (1 byte ascii)
-LF = 0AH (1 byte ascii)
-02 = Number of bytes read
-D1 = not used
-D2 = b7 b6 b5 b4 b3 b2 b1 b0 bit
0 0 - - - 0 - - ==> 10 minutes
0 1 - - - 0 - - ==> 15 minutes
1 0 - - - 0 - - ==> 20 minutes
1 1 - - - 0 - - ==> 30 minutes
0 0 - - - 1 - - ==> 60 minutes
0 1 - - - 1 - - ==> 1 minutes
1 0 - - - 1 - - ==> 2 minutes
1 1 - - - 1 - - ==> 5 minutes
E.g. :
-Integration Time = 15’
Reading string :
: 01 03 0000 0001 FB cr lf
Response from MICROVIP3 PLUS :
: 01 03 02 01 40 B9 cr lf
- Reading in eeprom of the flags for selection of the Star/Delta switching
P.C. MICROVIP3 PLUS
:,AA,03H,0000,0001, LRC, CR,LF ------>
<------ :,AA,03H,02,D1,D2,LRC,CR,LF
where:
-AA = 01 = address of the MICROVIP3 PLUS selected(2 bytes ascii)
-03H = Code of the command for reading of N words(2 bytes ascii)
-0000 = address from which the reading starts (4 bytes ascii)
-0001 = Number of words to be read (2 bytes ascii)
-LRC = Longitudinal Redundancy Check (2 bytes ascii)
-CR = 0DH (1 byte ascii)
-LF = 0AH (1 byte ascii)
-02 = Number of bytes read
-D1 = not used
-D2 = b7 b6 b5 b4 b3 b2 b1 b0 bit
- - - - 0 - - 0 ==> Star
- - - - 0 - - 1 ==> Delta
E.g. :
-Insertion "Delta"
Reading string :
: 01 03 0000 0001 FB cr lf
Response from MICROVIP3 PLUS :
: 01 03 02 01 51 A8 cr lf

Related product manuals