PAR. DESCRIPTION RANGE APP1 APP2 APP3 APP4 M.U.
CA1 Calibration 1. Temperature value to be added to the Pb1 value -12,0...+12,0 0,0 0,0 0,0 0,0 °CF
CA2 Calibration 2. Temperature value to be added to the Pb2 value -12,0...+12,0 0,0 0,0 0,0 0,0 °CF
CA3 Calibration 3. Temperature value to be added to the Pb3 value -12,0...+12,0 0,0 0,0 0,0 0,0 °CF
ddL
Display mode during defrost. 0 = display the temperature recorded by Pb1;
1 = lock recorded value of Pb1 at defrost start; 2 = display the “dEF” label
0/1/2 0 0 0 0 num
Ldd Timeout value for display unlock - dEF label 0 ... 255 30 30 30 30 min
dro
Select the unit of measurement used when displaying the temperature recorded by the
probes. (0 = °C, 1 = °F).
NOTE: switching between °C and °F or vice-versa DOES NOT modify the SEt,
diF values, etc. (e.g. Setpoint=10°C becomes 10°F)
0/1 0 0 0 0 flag
ddd
Selects the type of value to display.
0 = Setpoint; 1 = probe Pb1; 2 = probe Pb2; 3 = probe Pb3.
0/1/2/3 1 1 1 1 num
HACCP (“HCP” folder)
SHH Maximum HACCP alarm signals threshold. -55,0...150
0 10 0 0
°CF
SLH Minimum HACCP alarm signals threshold. -55,0...150 0 -10 0 0 °C/°F
drA
Minimum time spent in critical range for the event to be recorded. After this a HACCP
alarm will be triggered and logged.
0 ... 99 0 10 0 0 min
drH HACCP alarm reset time after last reset. 0 ... 250 0 24 0 0 hours
H50
Enable HACCP and alarm relay functions. 0= HACCP alarms NOT enabled;
1 = HACCP alarms enabled and alarm relay NOT enabled;
2 = HACCP alarms enabled and alarm relay enabled.
0/1/2 0 1 0 0 num
H51 HACCP alarm exclusion time. 0 ... 250 0 0 0 0 min
CONFIGURATION (“CnF” folder)
H00 Probe type selection. 0 = PTC; 1 = NTC; 2 = PT1000. 0/1/2
1 1 1 1
num
H11
Configuration of digital input 1/polarity.
0 = disabled; ±1 = defrost; ±2 = economy Setpoint; ±3= AUX;
±4= door switch; ±5 = external alarm; ±6= Standby; ±7= pressure switch;
±8= Deep Cooling; ±9= disable HACCP alarm logging.
NOTE: • the “+” sign indicates that the input is active if the contact is closed.
• the “-” sign indicates that the input is active if the contact is open.
-9 ... +9 2 0 4 2 num