POWER & ENERGY MEASUREMENT RANGE RESOLUTION ACCURACY
Active Power ±5kW x CT Ratio x PT
Ratio
10mW ±0.2%
Reactive Power ±5kVAr x CT Ratio x PT
Ratio
10mVAR ±2%
Apparent Power ±5kVA x CT Ratio x PT
Ratio
10mVA ±0.2%
Active Energy ±5kWh x CT Ratio x PT
Ratio
10mWh ±0.2%
Reactive Energy ±5kVArh x CT Ratio x PT
Ratio
10mVArh ±2%
Apparent Energy ±5kVAh x CT Ratio x PT
Ratio
10mVAh ±0.2%
True Power Factor ±1 (CAP\IND) 10µ ±0.2%
Displacement Power Factor ±1 (CAP\IND) 10µ ±0.2%
FLICKERING MEASUREMENT RANGE RESOLUTION ACCURACY
P
SST
, P
ST
10 Minutes, S
PLT
,
P
LT
2 Hours, L
PLT
0 to 20 0.01 ±5%
PST
INST
0 to 20 0.01 ±8%
UNBALANCE MEASUREMENT RANGE RESOLUTION ACCURACY
Volts (Negative & Zero
Seq.) Ratio
0 to 100% 0.1% 0.15%
Current (Negative & Zero
Seq.) Ratio
0 to 100% 0.1% 0.5%
TRANSIENT CAPTURE ACCURACY
Minimum Detection
Duration
78.1 μs (G4410)
39 μs (G4420)
19.5 μs (G4430)
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com