Insert the terminal block into the Voltage Sampling inputs:
Attach lugged ends of wires to the terminal block securing it with an
applicable sized screw driver,
Verify the correct voltage polarity of the terminal.
WARNING
You need to install a 2A Fuse and/or Circuit Breaker in series to the
instrument’s Voltage Sampling Input Terminals according to local wiring
codes.
Powering down the instrument does not remove voltage from the
voltage sampling terminals.
NOTE NOTE NOTE ...
The Ground input is the reference for all channels therefore it is
essential to connect it properly.
SEE ALSO
G4K Wiring
Wiring the Current Connections
Connect the AC/DC Supply Terminal
Connect the 48VDC Input
Establish 1st Time Connection