EasyManua.ls Logo

Elstat ems55advanced - Fan Cycle off (FCF); Fan Cycle on (FCO); Fan Set Point (FSP)

Elstat ems55advanced
84 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10.24 fan cycle off (FCF)
The table below details the fan cycle off (FC F) parameter.
display
description Defines the inactive period of the evaporator fan while the compressor is switched off.
considerations
Fan cycle is the fan cycle on (FC O) time + the fan cycle off (FC F) time.
Not used on the ems25
+
range 1 to 30 minutes
global default
1 minute
ems75sz: 20 minutes
10.25 fan cycle on (FCO)
The table below details the fan cycle on (FC O) parameter.
display
description Defines the active period of the evaporator fan while the compressor is switched off.
considerations
Fan cycle is the fan cycle on (FC O) time + the fan cycle off (FC F) time.
Not used on the ems25
+
range 1 to 30 minutes
global default
30 minutes
ems75sz: 5 minutes
10.26 fan set point (FSP)
The table below details the fan set point (FSP) parameter.
display
description
Prevents excessive condensation on the evaporator in environments where warm, and presumed
humid, air is present by operating the evaporator fan.
If the fan set point (FSP) temperature is exceeded, the evaporator fan running continuously even if the
door is opened.
On reaching set point (SP) temperature, the evaporator fan switches off during door openings.
considerations
Not related to fan cycle on (FC O) or fan cycle off (FC F).
Not used with OFCfirmware or the ems25
+
range 01 to 30ºC (33 to 86ºF)
global default 15ºC (59ºF)
ems55advanced and ems55Radvanced / General Use
75 of 84

Table of Contents

Other manuals for Elstat ems55advanced

Related product manuals