EasyManuals Logo

Elstat ems75sz User Manual

Default Icon
87 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #24 background imageLoading...
Page #24 background image
No. Parameter Please see: Notes:
18 See "Defrost interval (dE)" on page 73
19 See "Defrost duration (dd)" on page 73
20 See "Defrost method (dF)" on page 73
21
See "Defrost termination method (dtF)"
on page 74
22 See "Fan cycle on (FCO)" on page 74
23 See "Fan cycle off (FCF)" on page 74
24 See "Display stability (d2)" on page 75
25 See "Buzzer enable (b0)" on page 75
26 See "Buzzer duration (b1)" on page 76
27 See "Alarm delay (Ad)" on page 76
28 See "Activity frequency (AF)" on page 76
29
See "Motion sensor enable (Sn)" on page
77
30
See "Saving temperature disable (PEr)"
on page 77
31 See "Learning period (LP)" on page 77
32 See "Display (dIS)" on page 78
33 See "Marketing mode (Ar)" on page 78
34 See "Defrost heater (dHr)" on page 78 Sub-zero exclusive parameter
4.8 How to run the test routine (tst)
The test routine tests the following:
l Allload relays
l Analogue inputs (temperature sensors and door switch)
l Motion sensor.
Should a problem be suspected with the ems, it is recommended that the test routine is carried out
before disconnecting or replacing the EMS controller. The test routine can detect any loose or dis-
connected cables and check that the EMS is connected properly to the lights, fan and compressor.
23 of 86
27 February 2014

Table of Contents

Other manuals for Elstat ems75sz

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Elstat ems75sz and is the answer not in the manual?

Elstat ems75sz Specifications

General IconGeneral
BrandElstat
Modelems75sz
CategoryController
LanguageEnglish

Related product manuals