Display
Description Provides the option for a time-based or temperature-based defrost cycle.
Considerations
None
Available only with the ems55 series using OFC (Open Front Cooler) firmware
and the ems75sz.
Range 00 (time-based) or 01 (temperature-based)
Global default 00 (time-based)
9.24 Defrost termination method (dtF)
The table below details the defrost termination method (dtF) parameter.
Display
Description
Provides the option to end a defrost cycle as follows:
l
on the defrost duration (dd) only
l
on defrost duration (dd) or defrost termination temperature
(dtd).
If the defrost termination method (dtF) is set to use the defrost duration (dd)
or the defrost termination temperature (dtd), the EMS controller ends the
defrost cycle on the first to occur.
Considerations
Defrost method (dF) must be set to 0
Available only with the ems55 series using OFC (Open Front Cooler) firmware
and the ems75sz.
Range 00 (time[dd]) or 01 (time[dd] or temperature[dtd])
Global default 01 (time or temperature)
9.25 Fan cycle on (FCO)
The table below details the fan cycle on (FCO) parameter.
Display
Description
Defines the active period of the evaporator fan while the compressor is
switched off.
Considerations Fan cycle is the fan cycle on (FCO) time + the fan cycle off (FC F) time.
Range 1 to 30 minutes
Global default
30 minutes
ems75sz: 5 minutes
9.26 Fan cycle off (FCF)
The table below details the fan cycle off (FCF) parameter.