The table below describes the values for activity frequency (AF).
Value Name Description
00 Low frequency 1 door opening or 1 motion count
01 Medium frequency 1 door opening or 3 motion counts
02 High frequency 2 door openings or 6 motion counts
03 Automatic
The EMS controller runs continuously for 48 hours in the
ready mode. After 48 hours, the EMS controller sets the value
of the activity frequency to 0, 1, or 2.
Note:
l
If AF is set to 3, the EMS controller must run continuously for 48 hours to set the value of the activity frequency.
If power is lost during the 48 hour period, the EMS controller restarts the 48 hour period.
The EMS controller must complete the 48 hour period to determine the activity frequency before starting the
1-day or 7-day learning period.
9.32 Motion sensor enable (Sn)
The table below details the motion sensor enable (Sn) parameter.
Display
Description Enables the input from the motion sensor.
Considerations Must be disabled if a motion sensor is not fitted.
Range 00 (disabled) or 01 (enabled)
Global default 01 (enabled)
9.33 Saving temperature disable (PEr)
The table below details the saving temperature disable (PEr) parameter.
Display
Description
Disables the saving mode temperature so that the EMS controller maintains
the ready mode temperature at all times.
Disabling the saving mode temperature does not affect the light functionality.
Considerations None
Range 00 (off) or 01 (on)
Global default 00 (off)
9.34 Learning period (LP)
The table below details the learning period (L P) parameter.