6.3.3 Calibration 1 (CA1)
Display
Description Calibrates or adds an oset to temperatures measured by the appliance sensor.
Considerations Applied to all temperatures measured on the appliance sensor.
Range -4.0 to 4.0°C (-7 to 7°F)
Global default 0.0°C (0°F)
6.3.4 Compressor rest time (rt)
Display
Description
Denes the minimum time between compressor cycles.
The compressor rest time ensures that the pressures in the refrigeration system have
time to equalize during compressor o-cycles.
The compressor rest time (rt) helps to avoid the following:
Passing peak current through the windings of the compressor motor
Switching o the system on the thermal overload protection
Short cycling of the system.
Considerations
If set too low, the compressor rest time may cycle on the set point (SP) and
dierential (dIF) temperatures or the saving set point (SSP) and saving dierential (Sd)
temperatures.
Range 1 to 30 minutes
Global default 3 minutes
6.3.5 Delay to saving (dS)
Display
Description
Denes the delay in switching to the Saving mode from Ready mode.
The delay starts at the end of the last active 30 minute period of the Ready mode.
Considerations Set in multiples of 30 minutes.
Range 0 to 120 minutes (in multiples of 30 minutes)
Global default 0 (no delay)